Introduction
Safety Information
- Do not pierce the battery with nails, strike the battery with a hammer, step on the battery, drop the battery, or otherwise subject it to strong impacts or shocks. If a BBU is subjected to strong impacts or shocks, do not put it into service.
- Avoid high temperatures above 60 degrees Celsius.
- Perform daily inspections of battery storage areas.
-
-
Identify the failed BBU.
-
-
-
Press the retention lever towards the handle firmly and pull to release the BBU from the power shelf socket.
-
-
-
Insert a new BBU into the power shelf slot.
-
Press firmly until the BBU clicks into place. The click indicates that the BBU was seated properly.
-
-
-
Ensure the associated PSU LED displays solid green. This indicates that no failures have occurred.
-
Almost done!
This work is licensed under a Creative Commons Attribution 4.0 International License.
Conclusion
This work is licensed under a Creative Commons Attribution 4.0 International License.